Description Question: Shouldn’t the Single-Line-to-Ground (SLG) current flowing through the transformer be 800A & 10A for the generator since the Neutral Current Limit was set for both components?
What is the difference between the “
InitSymRMS SLG” datablock value and the “
InitRMS SLG Neutral” datablock value reported for both Generators & Transformers?
Answer: No, the Neutral Current is not the same as the Single-Line-to-Ground (SLG) current. The Neutral current is the summation of phases A, B, & C. The SLG current is only the highest phase current flowing to the Ground during the phase-to-ground fault. In Balance System Studies, phase A is faulted to ground and therefore Phase A will have the highest current during the fault.
Therefore, “InitSym RMS SLG” value is the highest phase current out of phases A, B, and C during the Phase-to-Ground fault coming out of the generator or Transformer. The “InitRMS SLG Neutral” value is the summation of Phases A, B, & C going through the neutral for the SLG fault.
Please keep in mind that if the license does not have the “Unbalance/Single-Phase” module, then you will not be able to see the individual phase currents reported on the datablock. Users without the UB/Single Phase module should look at the detailed Text Report of the SC study to view individual phase currents. The example attached will show differences using the unbalance short-circuit datablocks and comparing them to Balance Comprehensive Short-Circuit datablocks.
Example:The Balance System Study – Comprehensive SLG results are showing the following values in
Figure 1 for the SLG & the SLGNeutral coming out of the Generator (GEN1) and Transformer (MPT1) for a SLG fault at bus “B2-ABHK:
Figure 1: SLG results for fault at bus “B2-ABHK”.
If an Unbalance Single-Phase Short-Circuit study is performed with the same study setup as the Comprehensive Balance System study, then the following results are displayed in
Figure 2.
Figure 2: Comprehensive SC & UB SC results for SLG fault at bus “B2-ABHK”.
Notice how datablock “ubSC_InitSymSLG” & “ubSC_InitSymSLG Bus2” is displaying the Phase currents through generator & Transformer respectavily and the highest Phase current is matching the “InitSymRMS SLG” (generator) & “InitSymRMS SLG Bus2” (transformer) datablock values. These values added vectorially is the result SLG value reported at bus “B2-ABHK” for Phase A. Phases B & C at the faulted bus should be zero as shown above.
Now if we change the Datablock Formats “ubSC_initSymSLG Bus2” & “InitSymRMS SLG” to show the SUMMATION of Vectors A, B, & C (
Figures 3-4) you will see the following results shown in
Figure 5:
Figure 3: Datablock set to show Vector Summation of Phases A, B, & C.
Figure 4: Datablock set to show Vector Summation of Phases A, B, & C.
Figure 5: Same Study results, but now showing the Summation of Phase Currents reported by the “ubSC_InitSymSLG” values to show the Neutral Current flowing through the generator/transformer.
Notice how the values reported for generator datablock’s “InitRMS SLG Neutral” is the same as value for “unSC_InitSymSLG” which is summing the phase currents. Also, the same can be said for the Transformer for datablocks “InitRMS SLG Neutral Bus2” & “ubSC_InitSymSLG Bus 2”.
Note: There are cases when the SLG & SLG Neutral currents are the same, but not always. Below (
Figure 6) is an example showing the Transformer MPT1 out of service, changing Generator GEN1 to Swing-Bus, and re-running the Balance and Unbalance Comprehensive SC study:
Figure 6: Balance & UB SC results wit Transformer out-of-service & Generator set to Swing-Bus.