Equipment Evaluation Buses not Showing Up in Study
These are the conditions under which a bus will be evaluated or not. Note: Buses are evaluated based on whether or not the "Equipment Category" field is filled in.
The following rule is used if the Bus "Equipment Category" field is NOT filled in:
If the "Equipment Category" field is not filled in, and if the Continuous Rating, Short Circuit rating, Momentary rating, and Voltage Rating are zero, and there is no voltage drop problem, this bus is not evaluated.
If the "Equipment category field" is not filled in, and anyone of the ratings (Continuous, Short Circuit, Momentary, or Voltage) is not zero, and the Bus evaluation passes, this bus is not evaluated.
Otherwise, this bus is reported and evaluated.
The following rule is used if the Bus "Equipment category" field is filled in:
If the "Equipment Category" field is filled in, and the Continuous Rating, Short Circuit rating, Momentary rating, and Voltage Rating are zero, and there is no voltage drop problem, this bus is not
evaluated.
Otherwise, this bus is reported and evaluated.
If you use the latest PTW version (7.0.4.7) - There is a checkbox that automatically display all the buses.
Go to > Equipment Evaluation > Option > Evaluation Criteria

The following rule is used if the Bus "Equipment Category" field is NOT filled in:
If the "Equipment Category" field is not filled in, and if the Continuous Rating, Short Circuit rating, Momentary rating, and Voltage Rating are zero, and there is no voltage drop problem, this bus is not evaluated.
If the "Equipment category field" is not filled in, and anyone of the ratings (Continuous, Short Circuit, Momentary, or Voltage) is not zero, and the Bus evaluation passes, this bus is not evaluated.
Otherwise, this bus is reported and evaluated.
The following rule is used if the Bus "Equipment category" field is filled in:
If the "Equipment Category" field is filled in, and the Continuous Rating, Short Circuit rating, Momentary rating, and Voltage Rating are zero, and there is no voltage drop problem, this bus is not
evaluated.
Otherwise, this bus is reported and evaluated.
If you use the latest PTW version (7.0.4.7) - There is a checkbox that automatically display all the buses.
Go to > Equipment Evaluation > Option > Evaluation Criteria