- General Support Question
- Oneline & User Interface
- License Key Issues
- Downloading/Installing Software
- Printing
- Reports
- Equipment Modeling
- DAPPER (Demand Load)
- DAPPER (Load Flow)
- DAPPER (Short Circuit)
- CAPTOR (TCC)
- Arc Flash Evaluation
- Equipment Evaluation
- Cable Ampacity
- A_Fault (ANSI)
- IEC 60909 Fault
- IEC 61363 Fault
- TMS (Transient Motor Starting)
- HI_WAVE (Harmonics)
- Unbalanced/Single Phase
- GroundMat
- Cable-3D
- Scenario Manager
- Backup & Import/Export
Simulate LSIG breaker using "Function" in SKM
Please follow the below mentioned steps.
1) Find the appropriate breaker (having LSIG function) from list of Static Trip Breakers and select it in the TCC.
2) Click on Function/New/Name it as a Ground/Click on the Ground Function row/ under the sensors column select Neutral /Click on update/ hit OK.
3) Now you will have an option to select device from Library. Please refer to the second screenshot below.
4) Click on the Library/select the appropriate Ground Fault Breaker/ click Apply. You should see the Ground Fault curve in the same TCC.


1) Find the appropriate breaker (having LSIG function) from list of Static Trip Breakers and select it in the TCC.
2) Click on Function/New/Name it as a Ground/Click on the Ground Function row/ under the sensors column select Neutral /Click on update/ hit OK.
3) Now you will have an option to select device from Library. Please refer to the second screenshot below.
4) Click on the Library/select the appropriate Ground Fault Breaker/ click Apply. You should see the Ground Fault curve in the same TCC.