Simulate LSIG breaker using "Function" in SKM
Please follow the below mentioned steps.
1) Find the appropriate breaker (having LSIG function) from list of Static Trip Breakers and select it in the TCC.
2) Click on Function/New/Name it as a Ground/Click on the Ground Function row/ under the sensors column select Neutral /Click on update/ hit OK.
3) Now you will have an option to select device from Library. Please refer to the second screenshot below.
4) Click on the Library/select the appropriate Ground Fault Breaker/ click Apply. You should see the Ground Fault curve in the same TCC.