- General Support
- Oneline & User Interface
- License Key Issues
- Downloading/Installing Software
- Printing
- Reports
- Equipment Modeling
- DAPPER (Demand Load)
- DAPPER (Load Flow)
- DAPPER (Short Circuit)
- CAPTOR (TCC)
- Arc Flash Evaluation
- Equipment Evaluation
- Cable Ampacity
- A_Fault (ANSI)
- IEC 60909 Fault
- IEC 61363 Fault
- TMS (Transient Motor Starting)
- HI_WAVE (Harmonics)
- Unbalanced/Single Phase
- DC Systems Analysis
- GroundMat
- Cable-3D
- Scenario Manager
- Backup & Import/Export
How do I create a Retrofit Breaker
On most breakers you can interchange the trip units to create/model a retrofit breaker. Since SKM models the frame and the trip unit as one device, we also created a way toeasily model any static circuit breaker frame with any trip unit in the library. To Create aretro-fit, open PTW and then:
1.) Open up the PTW library (ptw.lib)
Steps: Document / Library / PTW library / OK / ptw.lib
2.) Go under Captor then Static breakers: You will notice that the Frame and Trip unit are listed under the “TYPE” column for each device.

We will create a retrofit breaker using a “H-3, FEDERAL PIONEER Frame” with a “RMS 210, CUTLER-HAMMER Trip Unit”.
3.) Create a copy of the device frame to be retrofitted in the “ptw.lib”.
Steps: Right Click on the device that contains the desired frame in the library, select
“Copy”. Then, go to Device > Paste (or right-click and select, Paste)

4.) Change the name of the newly pasted device to represent the new retrofit trip unit by double-clicking on the copy of the device to be retrofitted. Under “Notes” you could write a comment regarding this new device. (See picture below)

5.) Create the retrofit: Right-click on the device with the desired Trip Unit and select “Copy”. Then, Right-click on the newly created device (the desired Frame) and select “Replace Trip curves”

6.) You have now added a retrofit breaker to your library.
1.) Open up the PTW library (ptw.lib)
Steps: Document / Library / PTW library / OK / ptw.lib
2.) Go under Captor then Static breakers: You will notice that the Frame and Trip unit are listed under the “TYPE” column for each device.
We will create a retrofit breaker using a “H-3, FEDERAL PIONEER Frame” with a “RMS 210, CUTLER-HAMMER Trip Unit”.
3.) Create a copy of the device frame to be retrofitted in the “ptw.lib”.
Steps: Right Click on the device that contains the desired frame in the library, select
“Copy”. Then, go to Device > Paste (or right-click and select, Paste)
4.) Change the name of the newly pasted device to represent the new retrofit trip unit by double-clicking on the copy of the device to be retrofitted. Under “Notes” you could write a comment regarding this new device. (See picture below)
5.) Create the retrofit: Right-click on the device with the desired Trip Unit and select “Copy”. Then, Right-click on the newly created device (the desired Frame) and select “Replace Trip curves”
6.) You have now added a retrofit breaker to your library.