- General Support Question
- Oneline & User Interface
- License Key Issues
- Downloading/Installing Software
- Printing
- Reports
- Equipment Modeling
- DAPPER (Demand Load)
- DAPPER (Load Flow)
- DAPPER (Short Circuit)
- CAPTOR (TCC)
- Arc Flash Evaluation
- Equipment Evaluation
- Cable Ampacity
- A_Fault (ANSI)
- IEC 60909 Fault
- IEC 61363 Fault
- TMS (Transient Motor Starting)
- HI_WAVE (Harmonics)
- Unbalanced/Single Phase
- GroundMat
- Cable-3D
- Scenario Manager
- Backup & Import/Export
Formulas for multiplication factor for Resistace on higher order harmonics
For the 2-winding transformer, induction motor and generator, the factor is:
(1.0 + 0.1*Norder^1.5), where Norder is the order of the harmonics.
HVDC-AC Harmonic Interaction Part II -AC System Harmonic Model with Comparison of Calculated and Measured Data
Breuer, G.D.; Chow, J.H.; Gentile, T.J.; Lindh, C.B.; Addis, G.; Lasseter, R.H.; Vithayathil, J.J.;
Power Apparatus and Systems, IEEE Transactions

(1.0 + 0.1*Norder^1.5), where Norder is the order of the harmonics.
HVDC-AC Harmonic Interaction Part II -AC System Harmonic Model with Comparison of Calculated and Measured Data
Breuer, G.D.; Chow, J.H.; Gentile, T.J.; Lindh, C.B.; Addis, G.; Lasseter, R.H.; Vithayathil, J.J.;
Power Apparatus and Systems, IEEE Transactions