Why am I seeing small SLG values?

The generator connections are all set as WYE, so there is no ground for the zero seq. impedance network. This means that the Zzero is almost infinite, which is why the SLG current is almost 0. If you change any one of the generator connection to wye-ground, you will see a higher value for SLG current.