ARC FLASH MODULE

Greetings,

I have been working on several projects using SKM, specifically the arc flash module, to generate arc flash labels as the final deliverable. However, I have not been able to find a way to obtain or display the same arc flash parameters for equipment such as automatic transfer switches (ATS), disconnects with breakers or fuses, UPS systems, variable frequency drives (VFDs), or motor starters, as I can for panels and busbars.
In the detailed report generated by the arc flash module, only panels and/or busbars are shown, while the other equipment types are not included with their corresponding arc flash data.

Could you please advise if there is a way to configure SKM to display these parameters and include this equipment in the detailed arc flash reports?
RV
Ryan Vellia 2/25/2026 6:30 AM
What we do is simply add a bus (not a node bus) on the load side of the ATS and use that for our AIC/withstand rating as well as arc flash label.f